E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
177
I/O Menu Selection
Programming
5.3 I/O Menu Selection
Table 5.3.1 lists the I/O Menu selection and description.
5.4 CLOCK Menu Selection
Table 5.4.1 lists the Clock Menu selection and description.
5.5 MISC Menu Selection
This selection opens a
“MISC OPTS” Menu that al
lows the user to change the RS232 port Baud
rate, or perform a hard reset of the ILI-MB-E3/ILI95-MB-E3/ANX. Baud rate options are provided
to allow connection to a variety of printers. Table 5.5.1 lists the available Baud rates.
Although this change is temporary, it doesn
’t change the configuration.
5.6 LOG Menu Selection
Table 5.6.1 lists the Log Menu selection and description.
5.7 INFO Menu Selection
This selection displays the Firmware Version and time/date of the last configuration change in the
E3 Series
®
. It shows a code for the type of the most recent configuration update. The codes are as
follows:
1.
CAMWorks
™ Configuration Upload.
2.
Auto configuration (Options 1 or 2 on the Autoconfig Menu).
3.
Network node map change.
4.
Manual update via the
“CS” terminal command.
Menu Selection
Description
Output ON/OFF
Forces the toggling on or off of a specified output. These outputs can
include NAC 1, NAC 2, Municipal Circuit (if present) and any
Addressable Control Point.
Enable/Disable
Allows the user to take any addressable device on either SLC and
disconnect it through software. While disabled, a point will report a
trouble until it is enabled, but will not cause or respond to an alarm.
Table 5.3.1 I/O Menu Selection
Menu Selection
Description
Time
Is set in 24 hour notation. It is set with hours, then minutes
“HHMM”.
Date
Is set as month, date and year
“MMDDYY”.
Table 5.4.1 Clock Menu Selection
Baud Rates
• 115200
• 4800
• 19200
• 2400
• 9600
• 1200
Table 5.5.1 Baud Rates
Menu Selection
Description
Display Log
Opens the System Display to all events in the buffer memory.
Print Log
Sends the entire buffer memory to the RS-232 port.
Clear Log
(Hard reset) will eliminate all events stored in the buffer memory.
Sensitivity Report Will send sensor sensitivity information to the RS-232 port.
Table 5.6.1 Log Menu Selection