140
E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
E3 Series System Connections
ASM-16 Addressable Switch Connections
Designation
Description
Designation
TB1-2
TB1-2 LCD-7100
ASM-16 or ANU-48 to ASM-16 or ANU-48 Wiring
From ASM-16 or ANU-48
RS-485 COM A from previous device/to
TB1-3
+24V
Single Discrete Wire Connect To:
ASM-16 or ANU-48 to ASM-16 or ANU-48 Wiring
TB1-3
+24V
Single Discrete Wire TB1-3 +24V
TB3-6 ILI-MB-E3/ILI95-MB-E3
TB6-1 INI-VGC, INI-VGX, INI-VGE
TB1-4
GND
Single Discrete Wire
Common
Connect To:
TB1-4 GND
TB3-5
or
TB3-7
ILI-MB-E3/ILI95-MB-E3
TB6-4 INI-VGC, INI-VGX, INI-VGE
Note: See Note B in Figure 3.9.4.1 for the hardwire connection.
INI-VGC, INI-VGX or INI-VGE Wiring
From INI-VGC, INI-VGX or INI-VGE
To ASM-16 or ANU-48
J3 RS-485 Local
Ribbon Cable
J1, J2 or J3
Note: See Note C in Figure 3.9.4.1 for the ribbon cable connection.
From INI-VGC, INI-VGX or INI-VGE
To ASM-16 or ANU-48
ASM-16 or ANU-48 to ASM-16 or ANU-48 Wiring
TB6 RS-485 Remote
ASM-16 or ANU-48 TB-1
TB6-1
+24V
Single Discrete Wire TB1-3 +24V
TB6-2
COMM B
Single Discrete Wire TB1-2 COMM B
TB6-3
COMM A
Single Discrete Wire TB1-1 COMM A
TB6-4
GND
Single Discrete Wire TB1-4 GND
Note: See Note D in Figure 3.9.4.1 for the hardwire connection.
ILI-MB-E3/ILI95-MB-E3/ANX Wiring
From
ILI-MB-E3/ILI95-MB-E3/ANX
To ASM-16 or ANU-48
TB3-1
COMM A
Single Discrete Wire TB1-1 COMM A
TB3-2
COMM B
Single Discrete Wire TB1-2 COMM B
TB1-3
+24V
Single Discrete Wire TB1-3 +24V
TB1-4
GND
Single Discrete Wire TB1-4 GND
Note: See Note E in Figure 3.9.4.1 for the hardwire connection.
LCD-E3
From LCD-E3
To ASM-16 or ANU-48
J1
Ribbon Cable
J1, J2, or J3
Note: See Note F in Figure 3.9.4.1 for the ribbon cable connection.
Note2:
JMP1 - Termination leave out.
JMP2 - Factory Programming leave in.
JMP3 - Factory Programming leave in.
JMP4 - External Buzzer Connector.
Table 3.9.3.1 ASM-16 or ANU-48 Wiring Connections (Continued)