GENERAL
The BS-377/WP/A and BS-378/WP/A explosive
gas detectors are used to measure the
concentrations in % L.E.L. (Lower Explosive
L e v e l ) w h i l e s i m u l t a n e o u s l y p r o v i d i n g
autonomous notification/alarm operations in
case there is a leak of liquid on natural gas.
They are used in commercial and small
industrial areas such as professional kitchens
and burner rooms.
The installation must be done by trained
p e r s o n n e l t h a t h a s p r e v i o u s l y r e a d t h e
instruction manual.
In case on an alarm or gas leak:
Keep calm and follow the instruction below
independent of their order.
- Turn off all burning flames and anything that is
smoking.
- Close all gas appliances (kitchens - burners -
cookers etc.)
- Close the central gas supply or canister.
- Open doors and windows in order to ventilate
the area.
Avoid :
- Turning on/off the wall switches or the detector.
-Using a mobile phone in the area that is
Page
1
from
6
92137
700
0_09_007
Thank you for your trust in our products
Olympia Electronics - European manufacturer
BS-377/WP/A Autonomous waterproof liquid gas-LPG detector with relay
BS-378/WP/A Autonomous waterproof natural gas-methane detector with relay
II 3G
Ex ec IIA T6 Gc
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM CONSUMPTION
%
L.E.L ALARM
SENSOR TYPE
MEASUREMENT RANGE
SENSOR LIFE SPAN
SENSOR STABILIZATION PERIOD
DURING STARTUP
RESPONSE TIME
(Τ
90
)
REPEATABILITY
MAXIMUM DEVIATION
(
after calibration
)
CHANGE
INDICATORS
OUTPUTS
/
CONNECTIVITY
197-265V AC
catalytic
0-50
L.E.L.
5
years
(*)
60
seconds
<45
seconds
=
±
1.5 L.E.L.
≤
±
1.5 L.E.L.
≤
±
4.5 L.E.L./year
Operation LED
(
green
)
Fault LED
(
yellow
)
Alarm LED
(
red
)
Buzzer
Selectable at
10%
and
20%
L.E.L
3
VA (at
2
3
0
V AC)
OPERATION AND STORAGE
CONDITIONS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
IP
65
EN
60079-29-1, ΕΝ
5
0270, ΕΝ
5
0271
o
-10
to 60 C
1
atm
±
1
0
%
10
to 95% relative humidity
(
with no condensation
)
2 years
(**)
300gr.
145 x 85 x 45 mm
CONSTRUCTION MATERIAL
Bayblend FR3010
,
clear
polycarbonate
Alarm relay
(240
VAC /
5
A
N
.
O. /
2Α
N
.
C
.)
, latching/non-latching
Input for connecting an external button
(silence buzzer & alarm relay reset)
Fault relay (240VAC / 5A N.O.)
(*) =
(
Ideal conditions
)
When the detector is exposed to
cleaning agents, silicons and generally
in commercial and light industrial environments
, it is recommended to be calibrated every year
and
its sensor to be replaced every 3 years!
ATTENTION!! DO NOT USE LIQUID
GAS
(i.e. lighter
gas
) FOR SENSOR
TESTING
BECAUSE
IT
CAUSES PERMANENT DAMAGE. Use calibration gas up to 50% L.E.L. for this purpose.
(**) = does not cover the gas sensor, if it is exposed to Si, H2S, Pb & halogenated hydrocarbon.