background image

GENERAL

The  BS-377/WP/A  and  BS-378/WP/A  explosive 
gas  detectors  are  used  to  measure  the 
concentrations  in  %  L.E.L.  (Lower  Explosive 
L e v e l )   w h i l e   s i m u l t a n e o u s l y   p r o v i d i n g  
autonomous  notification/alarm  operations  in 
case  there  is  a  leak  of  liquid  on  natural  gas. 
They  are  used  in  commercial  and  small 
industrial  areas  such  as  professional  kitchens 
and burner rooms.
The  installation  must  be  done  by  trained 
p e r s o n n e l   t h a t   h a s   p r e v i o u s l y   r e a d   t h e  
instruction manual.

In case on an alarm or gas leak:
Keep  calm  and  follow  the  instruction  below 
independent of their order.

- Turn off all burning flames and anything that is 
smoking.
- Close all gas appliances (kitchens  - burners - 
cookers etc.)
- Close the central gas supply or canister.
-  Open  doors  and  windows  in  order  to  ventilate 
the area.

Avoid :

- Turning on/off the wall switches or the detector.
-Using  a  mobile  phone  in  the  area  that  is 

Page

 1

 from

 6

92137

700

0_09_007

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

BS-377/WP/A  Autonomous waterproof liquid gas-LPG detector with relay
BS-378/WP/A  Autonomous waterproof natural gas-methane detector with relay

II 3G

Ex ec IIA T6 Gc

TECHNICAL CHARACTERISTICS

OPERATION VOLTAGE
MAXIMUM CONSUMPTION

L.E.L ALARM

SENSOR TYPE
MEASUREMENT RANGE
SENSOR LIFE SPAN
SENSOR STABILIZATION PERIOD
DURING STARTUP
RESPONSE TIME

 (Τ

90

)

REPEATABILITY
MAXIMUM DEVIATION

 (

after calibration

)

CHANGE

INDICATORS

OUTPUTS 

CONNECTIVITY

197-265V AC

catalytic 

0-50 

L.E.L.

years

 (*)

60 

seconds

<45 

seconds

±

1.5 L.E.L.

 

±

1.5 L.E.L.

 

±

4.5 L.E.L./year

Operation LED

 (

green

)

Fault LED

 (

yellow

)

Alarm LED

 (

red

)

Buzzer

Selectable at

 10% 

and

 20% 

L.E.L

3

VA (at

 2

3

0

V AC)

OPERATION AND STORAGE
CONDITIONS

EXTERNAL DIMENSIONS  
TYPICAL WEIGHT 
GUARANTEE

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

IP

65

EN 

60079-29-1, ΕΝ 

5

0270, ΕΝ 

5

0271

o

-10

 to 60  C

atm 

±

1

0

%

10 

to 95% relative humidity

 (

with no condensation

)

2 years

 (**)

300gr.

145 x 85 x 45 mm

CONSTRUCTION MATERIAL

Bayblend FR3010

clear

 

polycarbonate

Alarm relay 

(240

VAC /

 5

A

 

N

.

O. /

 2Α 

N

.

C

.)

, latching/non-latching

Input for connecting an external button

(silence buzzer  & alarm relay reset)

Fault relay (240VAC / 5A N.O.)

(*) =

 

(

Ideal conditions

When the detector is exposed to 

cleaning agents, silicons and generally 

         in commercial and light industrial environments

, it is recommended to be calibrated every year

         and 

its sensor to be replaced every 3 years!

         ATTENTION!! DO NOT USE LIQUID

 GAS

 (i.e. lighter

 gas

) FOR SENSOR 

TESTING

 BECAUSE 

IT

 

         

CAUSES PERMANENT DAMAGE. Use calibration gas up to 50% L.E.L. for this purpose.

 

(**) = does not cover the gas sensor, if it is exposed to  Si, H2S, Pb & halogenated hydrocarbon.

Summary of Contents for BS-377/WP/A

Page 1: ...AGE MAXIMUM CONSUMPTION L E L ALARM SENSOR TYPE MEASUREMENT RANGE SENSOR LIFE SPAN SENSOR STABILIZATION PERIOD DURING STARTUP RESPONSE TIME Τ90 REPEATABILITY MAXIMUM DEVIATION after calibration CHANGE INDICATORS OUTPUTS CONNECTIVITY 197 265V AC catalytic 0 50 L E L 5 years 60 seconds 45 seconds 1 5 L E L 1 5 L E L 4 5 L E L year Operation LED green Fault LED yellow Alarm LED red Buzzer Selectable ...

Page 2: ... figure 2 to realize the external connections of the system The device operates with a mains voltage of 240V AC with a voltage range of 197 to 265V AC ATTENTION To maintain the degree of IP65 the waterproofing gasket must be fitted to the top of the chassis of the device Also after each opening of the chassis of the device the condition of the gasket should be checked and replaced if damage occurs...

Page 3: ...AY 5 BP111 can be used S4 This operation refers to the special operation calibration function with reference gas Via S4 select the concentration of gas that will be used 20 or 50 L E L S5 This setting refers to the concentration in L E L that must be detected in order to activate the alarm relay the red led and the buzzer 10 or 20 L E L can be selected After the selection is made the concentration...

Page 4: ...tor The red LED is activated when the gas concentration of L E L in the covered area exceeds the selected alarm level 10 or 20 The LED is deactivated when the gas concentration returns to normal levels If the latching function has been selected via the S3 micro switch then the LED remains active blinks every second even if the gas concentration drops to a safe level To deactivate it use the extern...

Page 5: ... and hold the button ΒΤ2 for more than 1 second to exit calibration mode and to return the detector to normal operation The red led is lit The clean air calibration procedure did not finish successfully Press and hold the button BT2 for more than 1 second to exit calibration mode and to return to normal operation You can repeat the process by following the steps from the beginning Calibration usin...

Page 6: ...the buyer does not follow the technical instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods provided or has any repairs or re setting done by a third party unless Olympia Electronics has fully agreed to them in writing Products that have been damaged can be returned to the premises of our company for repair or replacement as long as the warra...

Reviews: