COMMISSIONING
146
Service Manual
Part No.: 4417340 Revision 1
954 SmartServo FlexLine
Name
Explanation
Value Range
Default
[Gas immersion depth]
The minimum required
distance below an element
before it is taken into
account in the average
Vapour temperature
calculation
floating point number:
<-x.x .. +x.x>
<0.5>
[High High alarm]
[High Alarm]
[Low Alarm]
[Low Low alarm]
4 Thresholds for activating
a related alarm status in the
Primary Value
floating point numbers:
<-x.x .. +x.x>
<+1.0E22>
[Alarm test enable]
Enables (
if
activated, see
next listed entity) the
simulation of one of the 4
alarms for a minute, by
simulating the actual
measured Primary Value is
below or above the alarm
threshold.
<enable>
<disable>
<disable>
[Alarm test]
Activates and selects at the
same time the Alarm test (if
enabled with the
[Alarm test
enable]
listed before, and the
4 alarm thresholds are
properly set).
[No Alarm]
[High High alarm]
[High Alarm]
[Low Alarm]
[Low Low alarm]
<No Alarm>
[Function identification]
The name of the current
function of this module.
This name is visible on the
HART SmartView.
13 characters
<Vapour temp.>
Summary of Contents for FlexLine SmartServo 954
Page 1: ...Service Manual 954 SmartServo FlexLine ...
Page 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Page 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Page 203: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 195 954 SmartServo FlexLine ...
Page 300: ...APPENDIX A 292 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Page 302: ...APPENDIX B 294 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...