COMMISSIONING
222
Service Manual
Part No.: 4417340 Revision 1
954 SmartServo FlexLine
Name
Value Range
Default Value
Description
[Contact 1 Stop
proof test]
Command
Terminates an active contact 1
proof test. Upon termination,
the normal process will resume
and contact 1 will close.
[Contact 1 proof
test interval]
< 1 – 3650 >
(days)
< 1825 >
The maximum time interval
permitted between contact 1
proof tests. If exceed and when
a contact 1 safe state is not
active, the contact 1 safety
function status will change to W
to signal a warning that a proof
test is overdue. The status code
will remain as NO ERROR.
[Contact 1 proof
test timeout]
< Auto timeout off >
< 5 minutes >
< 10 minutes >
< 20 minutes >
< 30 minutes >
< 5 minutes >
If not < Auto timeout off >, the
maximum time duration a
contact 1 proof test will remain
active. If exceeded the proof
test will automatically stop.
[Contact 1 proof
test elapsed
time]
(RO)
< 0 – 4,294,967,295 >
(days)
< 0 >
The elapsed time since the last
contact 1 proof test or since
commissioning if no contact 2
output proof test has been
executed.
Summary of Contents for FlexLine SmartServo 954
Page 1: ...Service Manual 954 SmartServo FlexLine ...
Page 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Page 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Page 203: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 195 954 SmartServo FlexLine ...
Page 300: ...APPENDIX A 292 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Page 302: ...APPENDIX B 294 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...