COMMISSIONING
120
Service Manual
Part No.: 4417340 Revision 1
954 SmartServo FlexLine
7.3.7.4.2 VITO Interface Types
For temperature and/or water level measurement, a proper VITO probe
must be connected to the FII-VT module, using a VITO interface.
There are 3 VITO interface types:
762 VITO MTT interface for 16-spot temperature
measurement
(
thermocouple principle
) and optionally a water bottom
measurement
762 VITO LT interface for 9-spot temperature measurement
(
thermo- couple principle
) and optionally a water bottom
measurement
762 VITO MRT interface for Multiple Resistance
Thermometer and multi-spot (
resistance variation principle
)
measurement
7.3.7.4.3 Commissioning
Commissioning Parameters for MTT/LT Probes
The following 9 configurations are possible:
Enraf Model
VITO Type
Description
764C
MTT Temperature probe
lowest spot next to Pt100, no water probe
764D
lowest spot below Pt100, no water probe
766C
MTT Combi probe
lowest spot next to Pt100, combined with water probe
766D
lowest spot below Pt100, combined with water probe
767C
LT Temperature probe
lowest spot next to Pt100, no water probe
767D
lowest spot below Pt100, no water probe
768C
LT Combi probe
lowest spot next to Pt100, combined with water probe
768D
lowest spot below Pt100, combined with water probe
765
Water probe
water probe only
These models are depicted in
Figure 7-17
and
Figure 7-18
Summary of Contents for FlexLine SmartServo 954
Page 1: ...Service Manual 954 SmartServo FlexLine ...
Page 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Page 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Page 203: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 195 954 SmartServo FlexLine ...
Page 300: ...APPENDIX A 292 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Page 302: ...APPENDIX B 294 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...