COMMISSIONING
Part No.: 4417340 Revision 1
Service Manual
99
954 SmartServo FlexLine
In addition to the board’s
[Health]
LED LE1, the LEDs LE2 and LE3 are
available (see
Figure 7-7
). They can be associated to a relay, by setting
the
[LED Association]
entity.
☛
For a fail-safe level application, continue with section
7.3.6.10.
7.3.6.2 Operation Mode
The FII-DO can operate in one of two modes:
[Alarm Mode]
and
[Fallback Mode].
This is controlled by the
[Operation Mode]
entity.
Fallback Mode is not implemented yet.
☛
Set the [Operation Mode] entity to [Alarm Mode].
7.3.6.3 Relay Configuration
7.3.6.3.1 Jumper Settings
At installation, each individual relay contact was configured as required
with the hardware jumpers JPx0, where x = Relay 1 to 4 respectively.
See
Figure 7-8.
Figure 7-8
The relays’ hardware jumpers
NOTE: In the Commissioning stage, no jumper setting can be changed
without breaking the compartment screw sealing.