COMMISSIONING
Part No.: 4417340 Revision 1
Service Manual
135
954 SmartServo FlexLine
Name
Explanation
Value Range
Default
[Alarm test]
Activates and selects at the
same time the Alarm test (if
enabled with the
[Alarm test
enable]
listed before, and the
4 alarm thresholds are
properly set).
[No Alarm]
[High High
alarm]
[High
Alarm]
[Low Alarm]
[L
L
l
]
<No Alarm>
[Function identification]
The current module’s
function name. This
function is visible on the
HART SmartView
display.
13 characters
<Water level>
7.3.7.4.6 Commissioning Check
☛
After having checked/set all before listed entities, make sure
the [Board Commissioned], the [Product temperature
Commissioned], the [Vapour temperature
Commissioned], and - if applicable - the [Water level
Commissioned] entities are <True>;
the [Board Health], the [Product temperature Health],
the [Vapour temperature Health], and - if applicable - the
[Water level Health] entities are <GOOD>.