COMMISSIONING
76
Service Manual
Part No.: 4417340 Revision 1
954 SmartServo FlexLine
Name
Value Range
Default Value
Explanation
[Block mode]
<continuous>
<non continuous>
<continuous>
With this entity the user can
select whether the Block
command
remains active after the selected
interface has reached the
displacer.
Set to continuous the Block
command will
remain active until another
operational command with
sufficient priority
interrupts the Block command.
The displacer will follow the
interface.
Set non continuous the Block
command will also
be canceled if the product
reaches the displacer.
[Block]
This command stops the level
measurement,
See also Block mode
[Unlock]
This command is used to break
off any active operational
command.
After an Unlock command the
954 returns to the default
operation mode.
[Lock test]
This command will raise the
displacer up till it reaches [Motor
limit switch high] or [Lock test
limit level].
If motor limit high reached, the
displacer remains there (until
e.g. Unlock has been given)
If lock test limit reached, the
command mode will be changed
to Block.
[Lock test limit level]
<50.0>
Level at which the Lock test
command will stop the displacer
and the command mode will
change to Block.
[Calibrate]
This command will raise the
displacer up until it reaches the
calibration plate. This position
(innage level) will be compared
with [Tank top]. If the difference
is too big a fail is issued.
Summary of Contents for FlexLine SmartServo 954
Page 1: ...Service Manual 954 SmartServo FlexLine ...
Page 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Page 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Page 203: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 195 954 SmartServo FlexLine ...
Page 300: ...APPENDIX A 292 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Page 302: ...APPENDIX B 294 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...