COMMISSIONING
158
Service Manual
Part No.: 4417340 Revision 1
954 SmartServo FlexLine
7.3.9.7 Hardware Configuration
7.3.9.7.1 Jumper Allocation
The following are typical jumper settings done on the HCI-HAO board.
Jumper
Number
Position
Connection
Details
Description
Default
Position
Default
Connections
JP1
ON
Short 2 & 3
W&M Entity Protection
OFF
Short 1 & 2
JP2
ON
Short 2 & 3
Password Read Protection
OFF
Short 1 & 2
JP3
ON
Short 2 & 3
Write Protection All Entities
OFF
Short 1 & 2
JP4
ON
Short 2 & 3
Free
OFF
Short 1 & 2
JP5
ON
Short 2 & 3
Free
OFF
Short 1 & 2
JP6
ON
Short 2 & 3
CAN termination 120E resistor
OFF
Short 1 & 2
JP7 & JP8 A
Short 1 & 2
Active mode for Analog Output
A
Short 1 & 2
JP7 & JP8 P
Short 2 & 3
Passive mode for Analog Output
7.3.9.7.2 LED Allocation
LED
Number
Function
LE2
HART data Transmit
LE3
HART data Receive