COMMISSIONING
224
Service Manual
Part No.: 4417340 Revision 1
954 SmartServo FlexLine
Name
Value Range
Default Value
Description
[Contact 2
hysteresis]
< 0 – 3.402823 × 10
38
>
(meters)
< 0.010 >
A value relative to the
threshold that will determine
the point at which
deactivation of a contact 2
safe state occurs after
activation by an overfill or
underfill condition.
For an underfill, deactivation
occurs when the product
level is above (thr
hysteresis).
For an overfill, deactivation
occurs when the product
level is below (threshold –
hysteresis).
[Contact 2
safety function
status]
(RO)
Status:
< H >, < O >, < U >, < W >
Status Code:
Defined in Section
7.3.13.1
Status:
< H >
Status Code:
NO ERROR
H: Healthy
O: Overfill condition
U: Underfill condition
W: Warning condition, safe
state is active or proof test is
overdue
[Contact 2
safety shutdown
counter]
(RO)
< 0 – 3.402823 × 10
38
>
< 0 >
The number of contact 2 safe
state activations that have
occurred since
commissioning.
[Contact 2
safety shutdown
reason]
(RO)
Safety Function Status Code
NO ERROR
The safety function status
code identifying the reason
for the last time a contact 2
safe state activation
occurred.
Summary of Contents for FlexLine SmartServo 954
Page 1: ...Service Manual 954 SmartServo FlexLine ...
Page 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Page 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Page 203: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 195 954 SmartServo FlexLine ...
Page 300: ...APPENDIX A 292 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Page 302: ...APPENDIX B 294 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...