COMMISSIONING
Part No.: 4417340 Revision 1
Service Manual
153
954 SmartServo FlexLine
NOTE: Commands used in the following calibration procedure can be
executed either by using the CAN tool, the HART SmartView, or
Engauge.
Calibrate the analog output of the HCI-HAO as follows:
☛
Connect loop resistor at connector CN2
☛
Power up HCI-HAO board
☛
Give command [Enter Calibration Mode]
☛
Give command [Calibrate Analog Output at 4mA]
☛
Measure actual output current through the loop resistor, using a
current meter
☛
Enter this value in the
[Analog Output at 4mA]
entity
☛
Give command [Calibrate Analog Output at 18mA]
☛
Measure actual output current through the loop resistor, using a
current meter
☛
Enter this value in the
[Analog Output at 18mA]
entity
☛
Give command
[Exit Calibration Mode]
, to exit the calibration mode
These calibration data are used to calculate the analog output current
for the Primary Value (PV).
Until calibration has been carried out, the Health status of the PV and
the analog output function will be:
Status
<BAD>
Status Category
<STATUS_CATEGORY_BAD_GENERAL_CALIBRATION_FAIL>
Status Code
<CALIBRATION_SET_POINTS_NOT_CALIBRATED>
Summary of Contents for FlexLine SmartServo 954
Page 1: ...Service Manual 954 SmartServo FlexLine ...
Page 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Page 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Page 203: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 195 954 SmartServo FlexLine ...
Page 300: ...APPENDIX A 292 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Page 302: ...APPENDIX B 294 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...