COMMISSIONING
102
Service Manual
Part No.: 4417340 Revision 1
954 SmartServo FlexLine
☛
If
[Local] [Monitor Mode]
is to be set, skip to next bullet ().
☛
From the [Monitor Mode], select [Remote].
☛
Select
[Remote Threshold Source],
set desired value.
If the
[Monitor Mode]
is set to
[Local],
the scanned PV or SV
value is compared against the value set in the
[Threshold]
entity. The behavior is modified by the
[Threshold Mode]
and the
[Hysteresis]
entities. The
[Threshold Mode]
entity
can be set to either
<Treat as HA>
or
<Treat as LA>.
If the
[Threshold Mode]
entity is set to
<Treat as HA>,
the
relay is activated if the scanned PV or SV is greater than or
equal to the
[Threshold]
entity value, and the relay is
deactivated if the scanned PV or SV is less than the
[Threshold]
entity value minus the
[Hysteresis]
entity value.
If the
[Threshold Mode]
entity is set to <Treat as LA>, the
relay is activated if the scanned PV or SV is greater than or
equal to the
[Threshold]
entity value, and the relay is
deactivated if the scanned PV or SV is less than the
[Threshold]
entity value plus the
[Hysteresis]
entity value.
☛
From the [Monitor Mode], select [Local].
☛
Select
[Threshold Mode],
and choose either
<Treat as HA>
or
<Treat as LA>.
☛
Select
[Hysteresis],
set desired value.
7.3.6.4.3 Status Behavior
The Status Behavior entity determines what happens to the relay if the
health of the scanned PV or SV differs from Good. The
[Status
Behavior]
should be set to one of the following options:
<BAD>, <BAD-
UNCERTAIN>,
or
<Not Used>.
If the
[Status Behavior]
is set to
<BAD>,
and the scanned PV or SV
health is Bad, the respective relay will be activated.
If the
[Status Behavior]
is set to
<BAD-UNCERTAIN>,
and the scanned
PV or SV health is Bad or Uncertain, the respective relay will be
activated.
Summary of Contents for FlexLine SmartServo 954
Page 1: ...Service Manual 954 SmartServo FlexLine ...
Page 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Page 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...