COMMISSIONING
80
Service Manual
Part No.: 4417340 Revision 1
954 SmartServo FlexLine
Name
Value Range
Default Value
Explanation
[Upper reference level]
<27.0>
The upper reference level is
used to compute the ullage
level.
The ullage level is defined
as:
Ullage level = Upper
reference level - innage
level..
[Tank top level]
<100.0>
The Tank top level is used
during a calibration test to
determine if the calculated
innage is still within
acceptable range.
[Motor limit switch high]
<100.0>
The motor limit switch high
level indicates the highest
position the displacer
may reach during normal
operation.
This limit needs to be more
than 10 mm above the low
limit.
[Motor limit switch low]
<200.0>
The motor limit switch low
level indicates the lowest
position the displacer
may reach during normal
operation.
[Dip Height]
<0.3>
Determines how high the
displacer will stay above the
Interface 1 (Product level)
during dip mode.
[Dip interval time]
<60>
Determines the time in
between 2 consecutive
interface 1 dips
[Reference level]
<-100.0>
Level used to set the innage
product level.
[Accept reference]
This command sets the
innage product level
indicated by the reference
level.
Summary of Contents for FlexLine SmartServo 954
Page 1: ...Service Manual 954 SmartServo FlexLine ...
Page 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Page 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Page 203: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 195 954 SmartServo FlexLine ...
Page 300: ...APPENDIX A 292 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Page 302: ...APPENDIX B 294 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...