COMMISSIONING
Part No.: 4417340 Revision 1
Service Manual
123
954 SmartServo FlexLine
Product Temperature
☛
The following entities
must
be set by
Engauge
or
HART
SmartView
for a correct functioning of the FII-VT module in an
instrument.
NOTE: Using Engauge, following entities are set within the Engauge
Product temperature
tab.
Name
Explanation
Value Range
Default
[Lowest element offset]
The distance from tank zero
till the lowest element
position in the temperature
probe
floating point number:
<-x.x .. +x.x>
<80.0>
[Sensor length]
The distance from the
Pt100 position till the
highest element position
floating point number:
<-x.x .. +x.x>
<80.0>
The following entities
can
be set by
Engauge
or
HART SmartView
for a
correct functioning of the FII-VT module in an instrument.
☛
Check each entity for its correctness.
Name
Explanation
Value Range
Default
[Product immersion depth]
The minimum required
distance of the product
level above an element
before it is taken into
account in the average
product temperature
calculation
floating point number:
<-x.x .. +x.x>
<0.5>
[Hysteresis]
The distance for a
hysteresis mechanism
around the switching point
of the elements that are
taken into account in the
calculation
floating point number:
<-x.x .. +x.x>
<0.1>
[High High alarm]
[High Alarm]
[Low Alarm]
[Low Low alarm]
4 thresholds for activating a
related alarm status in the
Primary Value
floating point number:
<-x.x .. +x.x>
<+1.0E22>
Summary of Contents for FlexLine SmartServo 954
Page 1: ...Service Manual 954 SmartServo FlexLine ...
Page 197: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 189 954 SmartServo FlexLine ...
Page 202: ...COMMISSIONING 194 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Page 203: ...COMMISSIONING Part No 4417340 Revision 1 Service Manual 195 954 SmartServo FlexLine ...
Page 300: ...APPENDIX A 292 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...
Page 302: ...APPENDIX B 294 Service Manual Part No 4417340 Revision 1 954 SmartServo FlexLine ...