Operation
SDC / DHC
96
EN2H-0221GE51 R0812
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
03
Room connection
(in conjunction
with room sensor)
OFF
Display of heat
generator temperature,
room sensor off,
operation active
OFF
1
Display of room
temperature, room
sensor active, operation
active
2
Display of room
temperature, room
sensor active, operation
disabled
3
Display of room
temperature, room
sensor off, operation
active
04
Room factor
OFF
OFF
10 ...
500 %
Influence active
RC
Room controller active
07
Heating limit
OFF, 0.5 to 40 K
OFF
08
Room frost-
protection limit
5 ... 30
°
C
10
09
Room thermostat
function
OFF, 0.5 to 5 K
OFF
10
Assignment of
outside sensor
0
Regulation to average
value (outside sensor 1
+ outside sensor 2)
0
1
Regulation to outside
sensor 1
2
Regulation to outside
sensor 2