Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
11
Automatic exit
time
OFF
No automatic exit
2
0,5 ...
5 min
Automatic jump back to
the basic display occurs
after the set time
12
Anti-blocking
protection
ON
Anti-blocking protection
active
ON
OFF
Anti-blocking protection
not active
13
Logical fault
messages
OFF, ON
OFF
14
Automatic set
function
OFF, ON
OFF
15*
Locking code
for heating tech-
nician
OFF, 0001 to 9999
1234
16*
Type code
Controller type corresponding to
type code table
Type
18
Cycle
temperature
enable
OFF
Cycle temperature
disabled
ON
ON
Cycle temperatures
enabled
19
Frost-protection
mode
OFF
Continuous frost
protection as per
parameter 05
OFF
0.5 to
60 min
Cyclic operation