5.4.9 "Solar" menu (SOLAR)
The parameters in this menu refer to special settings with regard
to the solar applications.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
01
Switch-on
differential
(Setting value of parameter
02 + 3 K) to 30 K
10
02
Switch-off
differential
2 K to (setting value of parameter
01 – 3 K)
5
03
Minimum runtime
of solar charging
pump
0 ... 60 min
3
05
Buffer maximum
temperature limit
20 ... 110°C
75
06
Operating mode
1
Priority operation
2
2
Parallel operation
3
Priority operation of hot-
water circuit
4
Priority operation of
buffer
07
Heat generator
cycle inhibitor
(only if parameter
06 = 1)
OFF, 0.5 to 24 h
OFF
08
Solar priority
parallel switchover
OFF, 1 to 30 K
OFF
09
Heat balance
OFF
No heat balancing
OFF
1
Heat balancing via flow-
through calculation
2
Heat balancing via pulse
input
10
Reset heat
balance
SET by pressing the input button
–
11
Volume flow
0 ... 30 L/min or L/pulse
0
Summary of Contents for DHC
Page 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Page 2: ...EN2H 0221GE51 R0812 ...
Page 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Page 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Page 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Page 261: ......