See the table below for detailed correlations:
Buffer control mode
1
2
3
4
5
6
Buffer demand from
HC/HW
HC
HC/HW
HC
HC
–
Heat generator
demand from
BUFFER
BUFFER/
HW
BUFFER
BUFFER/
HW
BUFFER/
HW
HC/HW
Buffer control mode
Load
Load
Dis-
charge 1
Dis-
charge 1
Load
Dis-
charge 2
Buffer start-up
protection acts on
HC/HW
HC
HC/HW
HC
HC
–
Buffer discharge
protection
X
X
–
–
X
–
Buffer frost protection
monitoring
X
X
–
–
X
–
Buffer minimum
temperature monitoring
X
X
–
–
X
–
Buffer maximum
temperature monitoring
X
X
X
X
X
X
Buffer forced
dissipation into:
HC/HW
HC
HC/HW
HC
HC
HC/HW
Buffer siphon
function
X
X*
–
–
X*
–
Loading temperature
offset acts from:
HC/HW
HC
–
–
HC
–
Heat generator start-up
protection on buffer
loading pump
X
X
–
–
X
–
Buffer loading pump
with no demand
OFF
OFF
OFF
OFF
OFF
OFF
Buffer loading pump for
manual operation
ON
ON
OFF
OFF
ON
OFF
Buffer loading pump
function for sensor
defect
ON
ON
OFF
OFF
ON
OFF
Buffer loading pump
function for heat
generator disable
–
–
ON
ON
–
–
Summary of Contents for DHC
Page 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Page 2: ...EN2H 0221GE51 R0812 ...
Page 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Page 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Page 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Page 261: ......