SDC / DHC
Operation
EN2H-0221GE51 R0812
113
5.4.17 "Error messages 2" menu (ALARM 2)
Only in conjunction with heat generator interface
Error messages triggered by an automatic stoker are displayed in
this menu. The fault memory can hold max. 20 messages, which
can be displayed individually.
For this purpose, parameter 28 in the "System parameters" menu
must be set to ON.
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
01
Error message 1
Last error message
"Display"
02
Error message 2
Last error message but one
"Display"
03
Error message 3
Last error message but two
"Display"
04
Error message 4
Last error message but three
"Display"
...
20
Error message 20
First error message
"Display"
21*
Reset error
messages
SET by pressing the input button
–
* OEM
5.4.18 "Sensor calibration" menu (SENSOR ADJ.)
In this menu, all sensors connected to the central device can be
corrected by ±5 K based on the factory calibration value.
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
01
Outside sensor
–5 ... +5 K
0
02
Heat generator
sensor
–5 ... +5 K
0
03
Hot-water sensor
–5 ... +5 K
0
04
Flow sensor of
mixed heating
circuit 1
–5 ... +5 K
0
05
Flow sensor of
mixed heating
circuit 2
–5 ... +5 K
0
Summary of Contents for DHC
Page 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Page 2: ...EN2H 0221GE51 R0812 ...
Page 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Page 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Page 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Page 261: ......