SDC / DHC
Operation
EN2H-0221GE51 R0812
107
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
12
Density of medium 0.8 ... 1.2 kg/L
1.05
13
Heat capacity of
medium
2 ... 5 KJ/kgK
3.6
15
Test cycle of solar
charging
switchover
1 ... 60 min
10
16
Switchover tem-
perature
20 ... 110 °C
75
5.4.10 "Solid" menu (SOLID FUEL)
The parameters in this menu refer to special settings with regard
to solids regulation.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
01
Minimum
temperature
20 ... 80 °C
60
02
Maximum
temperature
30 ... 100 °C
90
03
Switch-on
differential
(Setting value of parameter
04 + 3 K) to 20 K
10
04
Switch-off
differential
2 K to (setting value of parameter
03 – 3 K)
5
05
Heat generator
cycle inhibitor
OFF, 2 to 180 min
OFF
5.4.11 "Buffer" menu (BUFFER)
The parameters in this menu refer to special settings with regard
to solids regulation.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.