Hydraulic Components
SDC / DHC
182
EN2H-0221GE51 R0812
The display of the unique heating circuit name appears
•
in the menu selection
•
in the parameter tree
•
on the information level
7.3.4.10 Room thermostat function (maximum room temperature limit)
This function determines a room temperature-related limit with
adjustable switching differential. If the room temperature of the
relevant heating circuit exceeds the current daytime or reduced
room setpoint by the set switching differential, heating is
temporarily stopped (heating circuit pump switched off).
Heating is resumed as soon as the room temperature of the
respective heating circuit drops 0.5 K below the switch-off
temperature.
Example:
Daytime room setpoint = 22°C
Thermostat function set value = 4 K
Interruption of heating:
T
Room
> (22°C + 4 K) > 26.0°C
Resumption of heating:
T
Room
> (26°C – 0.5 K) < 25.5°C
Set value OFF disables the thermostat function.
The thermostat function is effective while heating and in reduced
mode.
The thermostat function is disabled when outside temperature
frost protection is active.
5.4.4 "Direct heating circuit" menu (UNMIXED CIRC), Pg. 92
Function
NOTE
See also
Summary of Contents for DHC
Page 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Page 2: ...EN2H 0221GE51 R0812 ...
Page 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Page 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Page 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Page 261: ......