Operation
SDC / DHC
108
EN2H-0221GE51 R0812
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
01
Minimum
temperature
5 °C to setting value of parameter
02
20
02
Maximum
temperature
Setting value of parameter
01 to 95 °C
80
03
Boiler temperature
increase
–10 to 80 K
0
04
Buffer switching
differential
1 to 70 K
2
05
Forced discharge
OFF
OFF
1
In process water tank
2
In heating circuits
06
Follow-up switch-
on differential
OFF, (setting value of parameter
07 + 2 K) to 50 K
10
07
Follow-up switch-
off differential
1 K to (setting value of parameter
06 – 2 K)
5
08
Buffer start-up
protection
OFF
No start-up
protection
ON
Switching
differential
5 ... 20 K
5 K
09
Buffer discharge
protection
OFF
No discharge
protection
ON
ON
Discharge protection
active