Offset 0 - 100%
•
Default value 0%: Represents the valve start-up value (degree
of opening) in %. It functions as an offset to the current valve
position (0% means no accessing of the valve)
•
DT
min
: 2 … 20 K, factory value: 5 K
In case of a defect, the tank sensor or flow sensor switches off to
prevent scalding.
If hot-water loading is not activated, there is no setpoint for the
mixed heating circuit. The setpoint for the mixed heating circuit is
mandatory.
7.2.8 Mode of operation of hot-water control mode "external
operation"
If the energy supply for hot-water loading is not provided through
the district heating valve, no hot-water demand may be sent to the
heat generator. The following setting needs to be selected for this
case:
"Hot Water Circuit" menu, parameter 07 ("Hot-Water Circuit"
control mode) = 7 (external operation)
The hot-water pre-control is part of the hot-water loading.
Consequently, the request from storage control is forwarded to
the hot-water pre-control, which acts according to its function.
In the "Hot-Water Circuit" "External Operation" control mode, the
setpoint value from the hot-water pre-control is not forwarded to
the energy management unit (or the district heating valve).
Function
Summary of Contents for DHC
Page 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Page 2: ...EN2H 0221GE51 R0812 ...
Page 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Page 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Page 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Page 261: ......