Operation
SDC / DHC
102
EN2H-0221GE51 R0812
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
19
Modulation of
proportional range
X
P
0.1 ... 50 %/K
5
21
Modulation of
adjustment time T
n
1 ... 600 s
180
22
Modulation of
runtime
5 ... 600 s
12
23
Modulation of start
time
0 ... 900 s
60
24
Modulation of start
power
0 ... 100 %
70
25
Outside tempera-
ture lock (not if
parameter 01 =
OFF)
OFF, –20 to +30 °C
OFF
26
Base load
increase
0 ... 60 K
30
27
Minimum
temperature limit
of heating circuits
(only if parameter
02 = 3)
5 °C to setting value of parameter
03
36
28
Switching
differential of
minimum
temperature limit
of heating
circuits (only if
parameter 02 = 3)
2 ... 20 K
4
29
Heat generator
forced discharge
OFF
OFF
1
Discharge to process
water tank
2
Discharge to heating
circuits
3
Discharge to buffer tank