Operation
SDC / DHC
94
EN2H-0221GE51 R0812
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
12
Minimum
temperature limit
10°C to setting value of
parameter 13
20
13
Maximum
temperature limit
Setting value of parameter 12 to
Setting value of parameter 30 in
"Heat generator" menu (OEM
maximum limit)
75
14
Temperature
increase of heating
circuit
–5 ... 20 K
Direct
heating
circuit = 0
15
Extended pump
over-run
0 ... 60 min
5
16
Screed function
OFF
OFF
1
Functional heating
2
Screed-drying heating
23
Room control
C-factor (SDW 30
only)
1 ... 100
8
24
Room control T
n
(SDW 30 only)
5 ... 240 min
35
25
Holiday operating
mode
STBY Standby
STBY
RED
Lowering operation
26
Room setpoint
ramp
OFF, 0.5 to 60 K/h
OFF
41
Switch-on
optimisation
OFF
OFF
1
Adaption off
2
Adaption on
3
Adaption restart
42
Min. pre-heat time
0 ... setting value of parameter 43 0,5
43
Max. pre-heat time Setting value of parameter 42 to
30 h
5
44
Min. jump back
temperature
0 ... 30°C
5
45
Without room
sensor
0 ... 10°C
1
Summary of Contents for DHC
Page 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Page 2: ...EN2H 0221GE51 R0812 ...
Page 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Page 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Page 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Page 261: ......