Tank priority (no heating demand):
•
Connection immediately with minimum delay
•
Reversion with configured delay P3
Tank parallel operation (combined operation: hot-water
loading/heating)
•
Connection up to the stage of parameter 09 with minimum
delay for hot-water loading
•
In case of further need via heating, further connection with
configured delay of parameter 02
•
Reversion with configured delay parameter 03
7.3.5.2 Circulation pump (CIR.)
This function is only available, if a variable output is assigned to a
circulation pump
The output controls a hot-water circulation pump.
The use of the economy interval minimises the usual circulation
losses owing to adjustable switch-on intervals during operation
and determines the standstill time of the hot-water circulation
pump within an adjustable period (economy interval).
This parameter determines the length of the period and hence the
duration of the pause in a circulation pump pulse operating mode.
Economy interval
Pause
= Economy interval
Period duration
- Economy
interval
Pulse
The switching-on degree is calculated from the ratio:
n = Pulse time/Period duration x 100 (%)
Example:
NOTE
Function
Economy interval
(pulse)
Economy interval
(period duration)
Summary of Contents for DHC
Page 1: ...EN2H 0221GE51 R0812 Smile SDC heating and district heating controller SERVICE MANUAL ...
Page 2: ...EN2H 0221GE51 R0812 ...
Page 10: ...Contents SDC DHC 10 EN2H 0221GE51 R0812 ...
Page 36: ...Operation SDC DHC 36 EN2H 0221GE51 R0812 Operating overview ...
Page 66: ...Operation SDC DHC 66 EN2H 0221GE51 R0812 ...
Page 261: ......