Section 6: Message Formats
6-11
Message
Definition
Applies to
wired to the alarm control so that a si
gnal is sent to the
radio when the alarm is
Disarmed (Opening) or Armed
(Closing).
Note regarding the 7620ULF: Due to the fact that the
7620ULF is not a fire alarm control, supervisory faults
from the fire control panel may be used to trigger one or
more of the eight channels on the 7620ULF, and thus will
be reported as alarms. The central station should be
aware of which of the eight channels are actually
reporting supervisory conditions so alarm reports for
these channels can be responded to correctly.
cccc 5555 5551 7
AC Loss
7620ULF
only
cccc 5555 5553 7
AC Loss Restore
7620ULF
only
RCVB 5155 5555 7 While “Fail to manual” in LRR Line Card or 685 -
Automation – Auto button unchecked
7810iR-ent
RCVB 5551 5555 7 While “Fail to manual” in LRR Line Card or 685 -
Automation – Auto button checked
7810iR-ent
Status Channel = 8 (Alarm with low battery (older 7620 radio only)
NOTES: Each channel that displays these message types corresponds to a particular type of
event. Because there are eight channels, it is possible for multiple events to be reported in
multiple channels in only one message.
(Example: “cccc 1553 5155 8”
indicates an alarm on zone 1, a restore on zone 4 and a low
battery.)
Message
Definition
Applies to
cccc 5555 5555 8
Low Battery Massage
7620 or
7620ULF
only
cccc zzzz zzzz 8
Low Battery with Reported Alarms
Alarm messages are identical to those reported when the
status channel is a “7”. The “8” only indicates that a low
battery condition is also present. (Please refer to the
description of alarm messages for status channel of “7”.)
For these radios, the low battery message will be
repeated when other trouble conditions are reported
(where the status channel = ‘6’). The low battery
message will be sent directly following the trouble
message.
In addition, the low battery message will also be sent
when any alarm or restore is reported.
These radios do not have a specific Low Battery Restore
message. After a low battery condition is received, a
Low Battery Restore is implied when the next alarm or
Open/Close message is received with a ‘7’ in the ninth
channel rather than an ‘8’.
7620 or
7620ULF
only
Summary of Contents for AlarmNet 7810iR-ent
Page 2: ......
Page 22: ...7810iR ent Internet Intranet Alarm Receiver Installation and Setup Guide 3 4 ...
Page 66: ...7810iR ent Internet Intranet Alarm Receiver Installation and Setup Guide 5 10 ...
Page 86: ...7810iR ent Internet Intranet Alarm Receiver Installation and Setup Guide 6 20 ...
Page 97: ...Notes ...
Page 98: ...Notes ...
Page 99: ...Notes ...
Page 100: ...Notes ...
Page 101: ...Notes ...