7810iR-ent Internet/Intranet Alarm Receiver Installation and Setup Guide
2-10
UL
For UL installations, the DC power supply must be a UL Listed, regulated 12VDC, min. 500mA
Commercial Fire Alarm power supply, or two UL Listed Class 2 Honeywell Model 7720V2TRs
powered by a UL1481 Listed UPS with audible and visual indications of switchover to
secondary power.
ULC
For ULC installations, the DC power supply must be a CUL or CSA Listed, regulated 12VDC,
min. 500mA Commercial Fire Alarm power supply, or two UL Listed Class 2 Honeywell Model
7720V2TR-CNs powered by a CUL or CSA Listed Commercial Fire Alarm UPS with audible
and visual indications of switchover to secondary power.
Serial Printer Installation
The 7810iR-ent supports Okidata Microline 320 serial printers. The serial printer is
connected to 7810iR-ent using an RS232C link. All reports received by 7810iR-ent are also
printed on the connected printer. If a user manually acknowledges an alarm then “^^^ User
Ack ^^^” is printed after an alarm to indicate that the previous alarm was manually
acknowledged. The 7810iR-ent does not supervise the printer and will not generate any
alarm if the printer is out of paper or if the printer is disconnected.
ULC
Must use a ULC listed serial printer suitable for use in Central and Monitoring Stations.
(Such as a PRN-6 or PRN-6F serial printer.)
Serial Printer Configuration
Printer should be configured as follows -
Parity (none), Serial Data (8 bits), Baud rate (19200 bps);
Serial Printer Connection Summary
7810iR-ent Pin
Connects to Printer DB25 Connector Pin
6
2 (TX)
7
3 (RX)
3 (Ground)
7 (Signal ground)
* Pins 6 and 20 are shorted; (DTR and DSR)
Sample Printer Output
The following is a sample printer output when 7810iR-ent is in Auto or Manual mode.
NOTE: The first character in the line indicates the source of the alarm. C = AlarmNet-C
Radio, P = Private LAN and I = Internet.
Sample output for Manual Mode (User Acknowledgement is required)
P 15:19:22 06/22/04 00 0020 18 E 339 00 C803
^^^ User Ack ^^^
P 15:19:33 06/22/04 00 0020 18 E 341 00 C803
^^^ User Ack ^^^
P 15:20:24 06/22/04 00 0020 18 E 355 00 C000
^^^ User Ack ^^^
Sample output for Auto Mode (User Acknowledgement is NOT required)
P 15:19:22 06/22/04 00 0020 18 E 339 00 C803
P 15:19:33 06/22/04 00 0020 18 E 341 00 C803
P 15:20:24 06/22/04 00 0020 18 E 355 00 C000
Summary of Contents for AlarmNet 7810iR-ent
Page 2: ......
Page 22: ...7810iR ent Internet Intranet Alarm Receiver Installation and Setup Guide 3 4 ...
Page 66: ...7810iR ent Internet Intranet Alarm Receiver Installation and Setup Guide 5 10 ...
Page 86: ...7810iR ent Internet Intranet Alarm Receiver Installation and Setup Guide 6 20 ...
Page 97: ...Notes ...
Page 98: ...Notes ...
Page 99: ...Notes ...
Page 100: ...Notes ...
Page 101: ...Notes ...