Section 4: Programming
4-3
Action
Screen Display
6. For Private LAN configuration, select
Private LAN Only
.
Select the Account tab.
NOTE
: When
Private LAN Only
checkbox
is selected or deselected, 7810iR-ent
resets after “Back” or “Home” button is
pressed.
7. Enter
City ID
,
CS ID
and
Sub ID
by
touching each field and using the keypad.
In a Private System, the values for these
fields are not important, however, the same
City ID
and
CS ID
information must be
entered into all 7845i-ent’s being used in
the system.
Sub ID
must be unique for
each 7845i-ent being used in the system.
Record these numbers.
NOTE:
For AlarmNet-i the
City ID
,
CS ID
and
Sub ID
are provided by AlarmNet. For
Private LAN the
City ID
and
CS ID
, the first
two digits must be set to zero. The last two
digits can be set from 00 – FF. The
Sub
ID
can be set in the range of 0000 – FFFF.
NOTE: For Private LAN configuration, if
changing City ID and/or CS ID, clear the
database after making the changes.
The CLEAR DATABASE option is
located under Central Station, Clear
Database.
NOTE:
Do not select Use Master Account
# or
Enable Second CS
.
Select
Options
tab.
Summary of Contents for AlarmNet 7810iR-ent
Page 2: ......
Page 22: ...7810iR ent Internet Intranet Alarm Receiver Installation and Setup Guide 3 4 ...
Page 66: ...7810iR ent Internet Intranet Alarm Receiver Installation and Setup Guide 5 10 ...
Page 86: ...7810iR ent Internet Intranet Alarm Receiver Installation and Setup Guide 6 20 ...
Page 97: ...Notes ...
Page 98: ...Notes ...
Page 99: ...Notes ...
Page 100: ...Notes ...
Page 101: ...Notes ...