Section 2: 7810iR-ent Setup
2-5
ULC
For ULC installations, the DC power supply must be a CUL or CSA Listed, regulated 12VDC,
min. 500mA Commercial Fire Alarm power supply, or two UL Listed Class 2 Honeywell Model
7720V2TR-CNs powered by a CUL or CSA Listed Commercial Fire Alarm UPS with audible
and visual indications of switchover to secondary power.
UL
When using AlarmNet, a UL Listed cable/DSL router (externally powered) suited for the
application must be used.
12.
Attach the case front of the 7810iR-ent to the case back. Attach the top of the
7810iR-ent first, and then press the bottom section inward until it snaps into place
securely.
NOTE: For more information on networking, refer to the Communications Setup Section.
For general information on the 7810iR-ent, refer to the Navigation and Basic Features
Section. To complete the installation, refer to the Programming Section.
Figure 2a. 7810iR-ent 685-5 Line Card Mode Wiring using Honeywell Model 7720V2TRs
If using a UL Listed, regulated 12VDC, min. 500mA Commercial Fire Alarm power supply,
follow the method of wiring shown below.