7810iR-ent Internet/Intranet Alarm Receiver Installation and Setup Guide
6-8
Status Channel = 1 (Notification Message)
Message
Definition
Applies to
0000 5555 5555 1
Network Alert Message –
Tells the C/S to refer to their e-mail or fax machine for
further information and instructions from AlarmNet.
All
cccc 5555 1555 1
Secondary CS Communications Failure
A/M/C
cccc 5555 3555 1
Secondary CS Communications Failure Restore
A/M/C
Status Channel = 5 (Subscriber Trouble / Special Report)
Message
Definition
Applies to
Key Indicator: Account # = “0000” or “0001”
0000 5555 5515 5
0001 5555 5515 5
Master Host Alarm
The 685 generates this message internally. It indicates
a failure to connect to the network. This may be caused
by:
•
Antenna failure
•
Radio receiver failure
•
Substantial interference
•
Network outage
A, I & M
0000 5555 3555 5
0000 5555 5535 5
0001 5555 5535 5
Master Host Alarm Restore
A, I & M
0000 5555 1555 5
0001 5555 1555 5
Master Host Alarm Reminder
Notifies the central station that the redundant receiver
has lost connection to the 685.
M & I
0000 5155 5555 5
0001 5155 5555 5
Check 685 Printer
Tells the C/S to refer to their printer for messages that
might not be reported through the automation system.
A & M
NOTE: For subscriber reporting, each channel that displays these message types
corresponds to a particular type of event. Because there are eight channels, it is possible
for multiple events to be reported in multiple channels in only one message.
(Example: The message “cccc 1555 5355 5”
indicates a fault on zone 1 and a restore on
zone 6.)
cccc zzzz zzzz 5
Fire Zone Supervisory Fault
z = zone number corresponding to the channel position
(1 – 8)
1 = new zone fault
3 = zone restore
5 = normal zone condition
6 = previously report zone fault
7720ULF or
7920SE only
Summary of Contents for AlarmNet 7810iR-ent
Page 2: ......
Page 22: ...7810iR ent Internet Intranet Alarm Receiver Installation and Setup Guide 3 4 ...
Page 66: ...7810iR ent Internet Intranet Alarm Receiver Installation and Setup Guide 5 10 ...
Page 86: ...7810iR ent Internet Intranet Alarm Receiver Installation and Setup Guide 6 20 ...
Page 97: ...Notes ...
Page 98: ...Notes ...
Page 99: ...Notes ...
Page 100: ...Notes ...
Page 101: ...Notes ...