Section 6: Message Formats
6-5
Status Channel = 0 (Diagnostic Message)
Message
Definition
Applies to
Key Indicator: “F” in 2nd channel
cccc ngF0 s0fm 0
F-Type diagnostic (RF)
n = number of the node reporting (1-9, A-F)
g = node group number (0 or 1)
F = F-type diagnostic
s = signal strength (0-9, or A)
f = frequency (always “0”, not used)
m = modulation level (always “0”, not used)
A
cccc ngF0 s00t 0
F-Type diagnostic (pass/fail)
n = number of the node reporting (1-9, A-F)
g = node group number (0 or 1)
F = F-type diagnostic
0 = unused, always “0”
s = signal strength (0-9, or A)
00 = unused, always “00”
t = pass/fail result:
A = acceptable
F = failure
A
cccc nng4 rrrr 0
Subscriber Command Failure (Dialer reporting)
nn = number of the node reporting (01 to 15)
g = node group number (0 or 1)
4 = subscriber trouble message
rrrr = reason code:
0001 = Low signal strength
0002 = Frequency error
0003 = Modulation error
0004 = Keyed-on subscriber
0005 = Repeating alarm suppressed
0006 = Redundant supervision warning
0007 = Multiple nodes down
0010= Redundant supervision restore
0011 = Multiple nodes down restore
0012 = 2-Way radio internal tamper
0013 = Authentication – no response
0014 = Authentication violation
0015 = Authentication Initialized
* Messages for account # “0000” refer to the central
station.
A
Summary of Contents for AlarmNet 7810iR-ent
Page 2: ......
Page 22: ...7810iR ent Internet Intranet Alarm Receiver Installation and Setup Guide 3 4 ...
Page 66: ...7810iR ent Internet Intranet Alarm Receiver Installation and Setup Guide 5 10 ...
Page 86: ...7810iR ent Internet Intranet Alarm Receiver Installation and Setup Guide 6 20 ...
Page 97: ...Notes ...
Page 98: ...Notes ...
Page 99: ...Notes ...
Page 100: ...Notes ...
Page 101: ...Notes ...