8. Inspection and maintenance
Inspection and maintenance are necessary for safety operation. User must ensure the inspection and
maintenance are carried out as specified in the user’s manual.
Before performing inspection and maintenance, confirm the following items.
The machine or AGV monitored by UAM is switched OFF.
The surrounding of working environment is safe.
8.1 Pre-operation inspection
After configuring the UAM the authorized user should perform pre-operation inspection using a test piece.
It should be performed without connecting the sensor to the system.
Table 8-1 Pre-operation inspection list example
No.
Check item
Condition
Remark
Yes
No
1
UAM is correctly mounted at the intended location and
screws are firmly fastened
2
All the wirings are correct
3
The OSSD signal switches from ON state to OFF state
when the test piece is placed inside the protection zone
4
The OSSD signal remains in the OFF state when the test
piece is moved inside the protection zone
5
The OSSD signal switches from OFF state to ON state
when the test piece is removed from the protection zone
6
Area is switched and correctly displayed on UAM when
the input signals are changed according to the area
switching table
7
If UAM is in automatic restart mode, OSSD signal
switches from ON-state to OFF-state when the test piece is
placed inside the protection zone and switches from
OFF-state to ON-state when the test piece is removed
8
If UAM is in manual restart mode, OSSD signal switches
from ON-state to OFF-state when the test piece is placed
inside the protection zone and remains in OFF-state when
the test piece is removed
9
If the start interlock function is configured, starting the
UAM without placing the test piece in protection zone
causes the OSSD signal to remain in OFF-state until the
RESET signal is provided
10
If the muting function is configured, UAM terminates the
muting (OSSD switches to OFF-state) when the test piece
is placed inside the protection zone other than the muting
area even though the muting conditions are fulfilled.
Summary of Contents for UAM-05LP
Page 1: ... Document No C 61 00003 3 ...
Page 104: ... Document No C 61 00003 3 Figure 7 33 b Function Figure7 33 c Area ...
Page 107: ... Document No C 61 00003 3 Figure 7 36 a Project report tab Figure 7 36 b Error report tab ...
Page 148: ... Document No C 61 00003 3 13 External dimension 13 1 UAM 05LP ...
Page 149: ... Document No C 61 00003 3 13 2 Base mounting bracket ...
Page 150: ... Document No C 61 00003 3 13 3 Rear mounting bracket ...
Page 151: ... Document No C 61 00003 3 13 4 Cover Protection Bracket ...
Page 152: ... Document No C 61 00003 3 14 EC Declaration of conformity ...
Page 153: ... Document No C 61 00003 3 ...