Inverter
Appendix B
B–37
B089
Monitor display select
for networked inverter
R/W Selects the parameter
displayed on the keypad
display when the inverter is
networked, 7 options:
01... Output frequency
monitor
02... Output current monitor
03... Rotation direction
monitor
04... Process variable (PV),
PID feedback monitor
05... Intelligent input terminal
status
06... Intelligent output
terminal status
07... Scaled output frequency
monitor
10D8h 04312
1 to 7
—
B091
Stop mode selection
R/W Selects how the inverter stops
the motor, two option codes:
00... DEC (decelerate and
stop)
01... FRS (free run to stop)
10DA
h
04314
0, 1
—
B130
Over-voltage
LADSTOP enable
R/W Pauses deceleration ramp
when DC bus voltage rises
above threshold level, in order
to avoid over-voltage trip.
Two option codes:
00... Disable
01... Enable
10F5h
04341
0, 1
—
B131
Over-voltage
LADSTOP level
R/W Sets the threshold level for
over-voltage LADSTOP.
When the DC bus voltage is
above the threshold value, the
inverter stops deceleration
until the DC bus voltage is
less than the threshold setting
again.
10F6h
04342
330 to
390,
660 to
780
1 V
B150
Carrier mode (not
accessible to ModBus)
—
Automatically reduces the
carrier frequency as the
ambient temperature
increases.
Two option codes:
00... Disable
01... Enable
10F8h
04344
0, 1
—
“B” Group Fine Tuning Functions
Func.
Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.