“A” Group: Standard Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–12
The inverter has other control sources that can temporarily override the parameter A001
setting, forcing a different output frequency source. The following table lists all
frequency source setting methods and their relative priority (“1” is the highest priority).
The inverter also has other control sources that can temporarily override the parameter
A002 setting, forcing a different Run command source. The following table lists all Run
command setting methods and their relative priority (“1” is the highest priority).
Priority
A001 Frequency Source Setting Method
Refer to page...
1
[CF1] to [CF4] Multi-speed terminals
2
[OPE] Operator Control intelligent input
3
[F-TM] intelligent input
4
[AT] terminal
5
TM/PRG DIP Switch - (if switch is in “TM” position)
6
A001 Frequency source setting
Priority
A002 Run Command Setting Method
Refer to page...
1
[OPE] Operator Control intelligent input
2
[F-TM] intelligent input
3
TM/PRG DIP Switch - (if switch is in “TM” position)
4
A002 Run command source setting