Set Second Motor and Special-Set Second Motor
If you assign the [SET] or [S-ST] function to an intelligent input terminal, you can select
between two sets of motor parameters. The second parameters store an alternate set of
motor characteristics. Two type of inputs are available:
• Set Second Motor - The inverter can select a different motor only in Stop Mode.
• Special-Set Second Motor - The inverter can select a different motor in either Stop
Mode or Run Mode. The following parameter pairs can be alternately selected during
Run Mode: A020/A220, F002/F202, F003/F203, A042/A242, A043/A243, A061/
A261, A062/A262, A092/A292, A093/A293, A094/A294, A095/A295, A096/A296
When the terminal [SET] or [S-ST] is turned ON, the inverter will use the second set of
parameters to generate the frequency output to the motor. When changing the state of the
[SET] input terminal, the change will not take effect until the inverter is stopped.
When you turn ON the [SET] or [S-ST] input, the inverter operates per the second set of
parameters. When the terminal is turned OFF, the output function returns to the original
settings (first set of motor parameters). Refer to
“Configuring the Inverter for Multiple
Option
Code
Terminal
Symbol
Function Name
Input
State
Description
08
SET
Set (select) 2nd
Motor Data
ON
causes the inverter to use the 2nd set of motor
parameters for generating the frequency output
to motor. The selection of 1st or 2nd motor is
available only in Stop Mode.
OFF
causes the inverter to use the 1st (main) set of
motor parameters for generating the frequency
output to motor
53
S-ST
Special-Set (select)
2nd Motor Data
ON
causes the inverter to use the 2nd set of motor
parameters for generating the frequency output
to motor. The selection of 1st or 2nd motor is
available in Stop Mode or Run Mode.
OFF
causes the inverter to use the 1st (main) set of
motor parameters for generating the frequency
output to motor
Valid for inputs:
C001, C002, C003, C004,
C005
Required settings:
(none)
Notes:
•
If the terminal state for [SET] is changed while the
inverter is running, the inverter continues using the
current set of parameters until the inverter is
stopped.
•
You cannot configure the inverter to use [SET] and
[S-ST] terminals at the same time.
Example (requires input configuration—see
page
See I/O specs on page
1
2
3
4
5
L
PCS
SET
(or S-ST)
Summary of Contents for L200-002NFE2
Page 2: ......
Page 46: ......
Page 80: ......
Page 204: ......
Page 212: ......
Page 229: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 280: ......
Page 297: ...L2002 Inverter Appendix D D 5 L1 L2 L3 PE L2002 inverter with book type filter M 3 ...