L200
2
Inverter
Appendix B
B–29
A056
DC braking / edge or
level detection for [DB]
input
R/W Two options; select codes:
00... Edge detection
01... Level detection
1056h
04182
0, 1
—
A061
Frequency upper limit
setting
R/W Sets a limit on output
frequency less than the
maximum frequency (A004).
Range is from frequency
lower limit (A062) to
maximum frequency (A004).
0.0.. setting is disabled
>0.1 setting is enabled
105Ah
04186
(A062 x
10) to
(A004 x
10),
0=disable
>1=enabl
e
0.1 Hz
A261
Frequency upper limit
setting, 2nd motor
R/W
1517h
05399
A062
Frequency lower limit
setting
R/W Sets a limit on output
frequency greater than zero.
Range is start frequency
(B082) to frequency upper
limit (A061).
0.0.. setting is disabled
>0.1 setting is enabled
105Bh
04187
(B082 x
10) to
(A061 x
10),
0=disable
>1=enabl
e
0.1 Hz
A262
Frequency lower limit
setting, 2nd motor
R/W
1518h
05400
A063,
A065,
A067
Jump (center) frequency
setting
R/W Up to 3 output frequencies
can be defined for the output
to jump past to avoid motor
resonances (center frequency)
Range is 0.0 to 400.0 Hz
105Dh
1060h
1063h
04189
04192
04195
0 to 4000
0.1 Hz
A064,
A066,
A068
Jump (hysteresis)
frequency width setting
R/W Defines the distance from the
center frequency at which the
jump around occurs
Range is 0.0 to 10.0 Hz
105Eh
1061h
1064h
04190
04193
04196
0 to 100
0.1 Hz
A071
PID Enable
R/W Enables PID function,
two option codes:
00... PID Disable
01... PID Enable
1068h
04200
0, 1
—
A072
PID proportional gain
R/W Proportional gain has a range
of 0.2 to 5.0
1069h
04201
2 to 50
0.1
A073
PID integral time
constant
R/W Integral time constant has a
range of 0.0 to 150 seconds
106Ah
04202
0 to 1500
0.1 sec
A074
PID derivative time
constant
R/W Derivative time constant has a
range of 0.0 to 100 seconds
106Bh
04203
0 to 1000
0.1 sec
A075
PV scale conversion
R/W Process Variable (PV) scale
factor (multiplier), range of
0.01 to 99.99
106Ch
04204
1 to 9999
0.01
Holding Registers for “A” Group Standard Functions
Func.
Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.
Summary of Contents for L200-002NFE2
Page 2: ......
Page 46: ......
Page 80: ......
Page 204: ......
Page 212: ......
Page 229: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 280: ......
Page 297: ...L2002 Inverter Appendix D D 5 L1 L2 L3 PE L2002 inverter with book type filter M 3 ...