L200
2
Inverter
Conf
igur
ing
Dr
iv
e P
a
ra
m
e
ters
3–11
Run Command Source Setting -
For parameter A002, the following table provides a
further description of each option, and a reference to other page(s) for more information
A001/A002 Override Sources -
The inverter allows some sources to override the
settings for output frequency and the Run command in A001 and A002. This provides
flexibility for applications that occasionally need to use a different source, leaving the
standard settings in A001/A002. In particular, note the TM/PRG (Terminal/Program)
DIP switch behind the front panel cover shown below. It is the switch to the right.
The TM/PRG switch setting forces terminal operation, according to the table below:
When A001 = 01 and A002 = 01, the inverter control source is the terminals, regardless
of the TM/PRG switch position. When A001 and A002 setting is not 01, then the
TM/PRG switch can force terminal input control.
Code
Run Command Source
Refer to page(s)...
01
Control terminal - The [FW] or [RV] input terminals control
Run/Stop operation
02
Keypad Run key - The Run and Stop keys provide control
03
ModBus network input - The network has a dedicated coil
for Run/ Stop command and a coil for FW/RV
TM/PRG
Switch Position
Item
Source
PRG (Program)
Output frequency source
Specified by A001 setting
Run command source
Specified by A002 setting
TM (Terminal)
Output frequency source
[O] or [OI] analog input terminal
Run command source
[FW] and/or [RV] input terminals
SR
SK
OPE
485
PRG
TM