“B” Group: Fine Tuning Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–36
Note 1:
For inverter models 005NFE(F), 011NFE(F), and 030HFE(F), the overload-
related parameter settings are
different
from the rated amperes. Therefore, be
sure to set the electronic thermal overload according to the actual motor
driven by the particular inverter.
WARNING:
When parameter B012, level of electronic thermal setting, is set to motor
FLA rating (Full Load Ampere nameplate rating), the inverter provides solid state motor
overload protection at 115% of motor FLA or equivalent. If parameter B012 exceeds the
motor FLA rating, the motor may overheat and be damaged. Parameter B012, level of
electronic thermal setting, is a variable parameter.
Inverter Model
B012/B212
(A)
B022
(A)
C041
(A)
Inverter rated
Amperes (A)
–004NFE(F)
2.60
3.90
2.60
2.60
–005NFE(F)
4.00
6.00
4.00
3.00
–007NFE(F)
4.00
6.00
4.00
4.00
–0011NFE(F)
7.10
10.65
7.10
5.00
–015NFE(F)
7.10
10.65
7.10
7.10
–030NFE(F)
8.60
12.90
8.60
7.80
–040NFE(F)
8.60
12.90
8.60
8.60