ModBus Data Listing
Appendix B
B–36
B083
Carrier frequency
setting
R/W Sets the PWM carrier (inter-
nal switching frequency),
range is 2.0 to 14.0 kHz
10D2h 04306
20 to
140
0.1 Hz
B084
Initialization mode
(parameters or trip
history)
R/W Select the type of initializa-
tion to occur, two option
codes:
00... Trip history clear
01... Parameter initialization
02... Trip history clear and
parameter initialization
10D3h 04307
0, 1, 2
—
B085
Country code for initial-
ization (not accessible
to ModBus)
—
Select default parameter
values for country on initial-
ization. Note: Write not
allowed from network.
10D4h 04308
—
—
B086
Frequency scaling
conversion factor
R/W Specify a constant to scale the
displayed frequency for D007
monitor, range is 0.1 to 99.9
10D5h 04309
1 to 999
0.1
B087
STOP key enable
R/W Select whether the STOP key
on the keypad is enabled, two
option codes:
00... enabled
01... disabled
10D6h 04310
0, 1
—
B088
Restart mode after FRS
R/W Selects how the inverter
resumes operation when the
free-run stop (FRS) is
cancelled, two options:
00... Restart from 0Hz
01... Restart from frequency
detected from real speed of
motor (frequency matching)
10D7h 04311
0, 1
—
“B” Group Fine Tuning Functions
Func.
Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.
Summary of Contents for L200-002NFE2
Page 2: ......
Page 46: ......
Page 80: ......
Page 204: ......
Page 212: ......
Page 229: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 280: ......
Page 297: ...L2002 Inverter Appendix D D 5 L1 L2 L3 PE L2002 inverter with book type filter M 3 ...