ModBus Data Listing
Appendix B
B–30
A076
PV source setting
R/W Selects source of Process
Variable (PV), option codes:
00... [OI] terminal (current in)
01... [O] terminal (voltage in)
02... Network
03... Calculate function output
106Dh
04205
0, 1, 2, 3
—
A077
Reverse PID action
R/W Two option codes:
00... PID input = SP – PV
01... PID input = –(SP – PV)
106Eh
04206
0, 1
—
A078
PID output limit
R/W Sets the limit of PID output as
percent of full scale,
range is 0.0 to 100.0%
106Fh
04207
0 to 1000
0.1 %
A081
AVR function select
R/W Automatic (output) voltage
regulation, selects from three
type of AVR functions, three
option codes:
00... AVR enabled
01... AVR disabled
02... AVR enabled except
during deceleration
1070h
04208
0, 1, 2
—
A082
AVR voltage select
R/W 200V class inverter settings:
00... 200
01... 215
02... 220
03... 230
04... 240
400V class inverter settings:
00... 380
01... 400
02... 415
03... 440
04... 460
05... 480
1071h
04209
0 to 5
—
A092
(high)
Acceleration (2) time
setting
R/W Duration of 2nd segment of
acceleration, range is:
0.01 to 3000 sec.
1074h
04212
1 to
300000
*1
0.1 sec
A092
(low)
R/W
1075h
04213
A292
(high)
Acceleration (2) time
setting, (2nd motor)
R/W Duration of 2nd segment of
acceleration, 2nd motor,
range is: 0.01 to 3000 sec
1518h
05400
1 to
300000
*1
0.1 sec
A292
(low)
R/W
1519h
05401
Holding Registers for “A” Group Standard Functions
Func.
Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.