15.6 Interlocking the pit
This shows how to interlock the CU 36X.
In the example, slave address 0x01 is used. Note that the register
is reset by the CIM 200 when the command has been
acknowledged. The value is only triggered on rising edge.
The register on address 00101 is set to the following:
Hence the value to set is 0b000000000010000 = decimal 16 =
0x0010.
Request from master to slave
Example of response from slave to master
If there is no response from the slave, see section
200 Modbus communication faults
.
Bit
Description
0
0 (do not reset)
1
0 (do not reset alarms)
2
0 (do not reset history)
3
0 (do not reset event log)
4
1 (interlock the pit)
5
0 (set pit in "Auto" mode)
Field
Value
Description
Slave address
0x01
-
Function code
0x06
Write single register
Start address HI
0x00
ControlRegister address
= 00101 (0x0065)
Start address LO
0x64
Value HI
0x00
ControlRegister value
= 16 (0x0010)
Value LO
0x10
Field
Value
Description
Slave address
0x01
-
Function code
0x06
Write single register
Start address HI
0x00
ControlRegister address
= 00101 (0x0065)
Start address LO
0x64
Value HI
0x00
ControlRegister value
= 16 (0x0010)
Value LO
0x10