English (GB)
41
00568
Pump4Current
0.1 A
Motor current.
00569
Pump4LatestCurrent
0.1 A
Latest motor current.
00570
Pump4Voltage
0.1 V
Voltage.
00571
Pump4Insulation
10 k
Ω
Motor insulation resistance.
00572
Pump4WaterInOil
0.1 %
Motor water-in-oil measurement.
00573
Pump4Alarms1
Bits
See section
00574
Pump4Alarms2
Bits
See section
00575
Pump4Alarms3
Bits
See section
00576
Pump4Warnings1
Bits
See section
00577
Pump4Warnings2
Bits
See section
00578
Pump4Warnings3
Bits
See section
00579
Pump4MotorTemperature1
1 °C
Motor temperature 1.
00580
Pump4MotorTemperature2
1 °C
Motor temperature 2.
00581
Pump4PowerHI
1 W
Power consumption.
00582
Pump4PowerLO
00583
Pump4EnergyHI
0.1 kWh
Energy consumption.
00584
Pump4EnergyLO
00585
Pump4CosPhi
0.01
Motor cos
φ
.
00586
Pump4Frequency
0.1 Hz
Motor-applied frequency.
00587
Pump4VFDmode
enum
Mode of variable-frequency drive.
0 = VFD not controlled
1 = -
2 = Stopped
3 = Reverse start
4 = Start flushing
5 = Normal
6 = Run flushing
7 = Stop flushing
8 = Specific-energy test.
00588
Pump4Torque
0.1 Nm
Motor torque.
00589
Pump4Asym
0.1 %
Line current asymmetry.
00590
Pump4Sensors.WIO
Bit 0: WaterInOilSensor
Bool
Presence of water-in-oil (WIO) sensor.
0 = Not present
1 = Present.
Pump4Sensors.Current
Bit 1: MotorCurrentSensor
Bool
Presence of current sensor.
0 = Not present
1 = Present.
00591
Pump4Alarms4
Bits
See section
00592
Pump4Warnings4
Bits
See section
00593
Pump4AntiBlockingCounter
Bits
Number of anti blockings in the pump
00594
Pump4AISetpointSelect
enum
Analog input used as setpoint for pump 4:
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00595
Pump4SetpointType
enum
Setpoint type for pump 4:
0 = Fixed value
1 = Analog input
00596
Pump4FeedbackSensorType
enum
Feedback sensor type for pump 4:
4 = Flow rate
5 = Level, pressure
6 = Level, ultrasound
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00597
Pump4ControlMode
enum
Control mode for pump 4:
0 = Fixed frequency
1 = Linear control
2 = Minimum control
3 = PID control
00598
Pump4ActualSetpoint
1 %
Actual setpoint for pump 4
00599
Pump4FixedFrequency
0.01 Hz
Fixed frequency for pump 4