9.5 Pit control and configuration register block
Registers in this block can be read by means of function codes
0x03 and/or 0x04. They can be written as holding registers with
function codes 0x06 and 0x10.
Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address
Register name
Scale
Description
00101
PitControl
Bit 0: ResetAlarm
Bool
Control bit that resets alarms and warnings from the CU 36X.
0 = No resetting
1 = Resetting alarm.
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
PitControl
Bit 1: RESERVED
-
-
PitControl
Bit 2: ResetEventLog
Bool
Control bit that resets the SCADA event log in the CU 36X.
0 = No resetting
1 = Resetting event log.
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
PitControl
Bit 3: InterlockPit
Bool
Control bit that interlocks the pit (stops all pumps) for a specified time
interval (see the InterlockTimeout register 00226), meaning that the pit will
automatically go back to "Auto" mode after timeout.
0 = No command
1 = Pit interlocked (status is read from OperatingMode register 00203).
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
PitControl
Bit 4: AutoPit
Bool
Control bit that sets the pit to "Auto" mode.
0 = No command
1 = Pit in "Auto" mode (status is read from OperatingMode register 00203).
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
PitControl
Bit 5: CallBackAck
Bool
Control bit that acknowledges a call-back from the CU 36X.
0: No command
1: Acknowledging the call-back.
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
PitControl
Bit 6: ResetUserDefCounter1
Bool
Reset the user-defined counter 1
0: No resetting
1: Reset counter
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
PitControl
Bit 7: ResetUserDefCounter2
Bool
Reset the user-defined counter 2
0: No resetting
1: Reset counter
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
PitControl
Bit 8: ResetUserDefCounter3
Bool
Reset the user-defined counter 3
0: No resetting
1: Reset counter
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
PitControl
Bit 9: CallBackTest
Bool
Activates the call-back test function
0: No command
1: Activates call-back test
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.