English (GB)
38
9.10 Pump 3 register block
All register values are read-only, and 0xFFFF indicates that the
data value is not available.
Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address
Register name
Scale
Description
00501
Pump3Status
Bit 0: Presence
Bool
Presence of pump.
0 = Not present
1 = Present.
Pump3Status
Bit 1: Running
Bool
Running state of pump.
0 = Not running
1 = Running.
Pump3Status
Bit 2: MonitoringFault
Bool
Fault state of pump monitoring devices.
0 = No fault
1 = Fault in auxiliary equipment or sensors.
Pump3Status
Bit 3: Warning
Bool
Warning state of pump.
0 = No warning
1 = Warning.
Pump3Status
Bit 4: Alarm
Bool
Alarm state of pump.
0 = No alarm
1 = Alarm.
Pump3Status
Bit 5: IO111Present
Bool
Presence of auxiliary equipment IO 111.
0 = Not present
1 = Present.
Pump3Status
Bit 6: IO111Fault
Bool
Fault state of auxiliary equipment IO 111.
0 = No fault
1 = Fault.
Pump3Status
Bit 7: MP204Present
Bool
Presence of auxiliary equipment MP 204.
0 = Not present
1 = Present.
Pump3Status
Bit 8: MP204Fault
Bool
Fault state of auxiliary equipment MP 204.
0 = No fault
1 = Fault.
Pump3Status
Bit 9: CUEPresent
Bool
Presence of auxiliary equipment CUE.
0 = Not present
1 = Present.
Pump3Status
Bit 10: CUEFault
Bool
Fault state of auxiliary equipment CUE.
0 = No fault
1 = Fault.
Pump3Status
Bit 11: PumpDisabled
Bool
Enabled/disabled state of pump.
0 = Enabled
1 = Disabled (e.g. for temporary maintenance).
00502
Pump3ControlSource
enum
Control source of pump.
0 = Auto
1 = Switch
2 = Display
3 = Remote-controlled by bus.
00503
Pump3ConnectionType
enum
Pump connection type.
0 = The pump is controlled from the CU 36X output relay.
1 = The pump is controlled from the IO 351B output relay.
2 = The pump is controlled from the CU 36X and VFD.
3 = The pump is controlled from the IO 351B and VFD.
00504
Pump3OperatingTimeHI
1 minute
Total operating time.
00505
Pump3OperatingTimeLO
00506
Pump3TimeToServiceHI
1 minute
Time to next service.
00507
Pump3TimeToServiceLO
00508
Pump3OperatingTimeYesterday
1 minute
Operating time yesterday.
00509
Pump3OperatingTimeToday
1 minute
Operating time today.
00510
Pump3LatestOperatingTime
1 second
Operating time last time it was operated.
00511
Pump3StartCounterHI
Unscaled
Total number of pump starts.
00512
Pump3StartCounterLO
00513
Pump3StartCounterYesterday
Unscaled
Total number of pump starts yesterday.
00514
Pump3StartCounterToday
Unscaled
Total number of pump starts today.
00515
Pump3StartsPerHour
Unscaled
Number of pump starts within the last hour.
00516
Pump3Flow
0.1 litre/s
Calculated average or measured pump flow.
00517
Pump3LatestFlow
0.1 litre/s
Latest calculated/measured flow (capacity).