English (GB)
43
00618
Pump5Current
0.1 A
Motor current.
00619
Pump5LatestCurrent
0.1 A
Latest motor current.
00620
Pump5Voltage
0.1 V
Voltage.
00621
Pump5Insulation
10 k
Ω
Motor insulation resistance.
00622
Pump5WaterInOil
0.1 %
Motor water-in-oil measurement.
00623
Pump5Alarms1
Bits
See section
00624
Pump5Alarms2
Bits
See section
00625
Pump5Alarms3
Bits
See section
00626
Pump5Warnings1
Bits
See section
00627
Pump5Warnings2
Bits
See section
00628
Pump5Warnings3
Bits
See section
00629
Pump5MotorTemperature1
1 °C
Motor temperature 1.
00630
Pump5MotorTemperature2
1 °C
Motor temperature 2.
00631
Pump5PowerHI
1 W
Power consumption.
00632
Pump5PowerLO
00633
Pump5EnergyHI
0.1 kWh
Energy consumption.
00634
Pump5EnergyLO
00635
Pump5CosPhi
0.01
Motor cos
φ
.
00636
Pump5Frequency
0.1 Hz
Motor-applied frequency.
00637
Pump5VFDmode
enum
Mode of variable-frequency drive.
0 = VFD not controlled
1 = -
2 = Stopped
3 = Reverse start
4 = Start flushing
5 = Normal
6 = Run flushing
7 = Stop flushing
8 = Specific-energy test.
00638
Pump5Torque
0.1 Nm
Motor torque.
00639
Pump5Asym
0.1 %
Line current asymmetry.
00640
Pump5Sensors.WIO
Bit 0: WaterInOilSensor
Bool
Presence of water-in-oil (WIO) sensor.
0 = Not present
1 = Present.
Pump5Sensors.Current
Bit 1: MotorCurrentSensor
Bool
Presence of current sensor.
0 = Not present
1 = Present.
00641
Pump5Alarms4
Bits
See section
00642
Pump5Warnings4
Bits
See section
00643
Pump5AntiBlockingCounter
Bits
Number of anti blockings in the pump
00644
Pump5AISetpointSelect
enum
Analog input used as setpoint for pump 5:
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00645
Pump5SetpointType
enum
Setpoint type for pump 5:
0 = Fixed value
1 = Analog input
00646
Pump5FeedbackSensorType
enum
Feedback sensor type for pump 5:
4 = Flow rate
5 = Level, pressure
6 = Level, ultrasound
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00647
Pump5ControlMode
enum
Control mode for pump 5:
0 = Fixed frequency
1 = Linear control
2 = Minimum control
3 = PID control
00648
Pump5ActualSetpoint
1 %
Actual setpoint for pump 5
00649
Pump5FixedFrequency
0.01 Hz
Fixed frequency for pump 5
Address
Register name
Scale
Description
Pumpland.ru