Pump alarms 4 (registers 00441 (pump 1), 00491 (pump 2), 00541 (pump 3), 00591 (pump 4), 00641 (pump 5), 00691 (pump 6))
Pump warnings 4 (registers 00442 (pump 1), 00492 (pump 2), 00542 (pump 3), 00592 (pump 4), 00642 (pump 5), 00692 (pump 6))
Leakage current
PumpAlarms/Warnings4.0
1
CUE, pump No [1; 6]
Signal fault, temperature 3 sensor
PumpAlarms/Warnings4.1
176
CUE, pump No [1; 6]
Signal fault, (feedback) sensor 1
PumpAlarms/Warnings4.2
89
CUE, pump No [1; 6]
Overcurrent
PumpAlarms/Warnings4.3
49
CUE, pump No [1; 6]
Motor current protection activated
PumpAlarms/Warnings4.4
55
CUE, pump No [1; 6]
Change bearings
PumpAlarms/Warnings4.5
30
CUE, pump No [1; 6]
Lubricate bearings
PumpAlarms/Warnings4.6
240
CUE, pump No [1; 6]
Automatic motor model recognition failed
PumpAlarms/Warnings4.7
242
CUE, pump No [1; 6]
Communication fault, twin-head pump
PumpAlarms/Warnings4.8
77
CUE, pump No [1; 6]
Signal fault, temperature 1 sensor
PumpAlarms/Warnings4.9
91
CUE, pump No [1; 6]
Dry running
PumpAlarms/Warnings4.10
57
CUE, pump No [1; 6]
VFD not ready
PumpAlarms/Warnings4.11
213
IO 351B, pump No [1; 6]
Other
PumpAlarms/Warnings4.12
16
CUE, pump No [1; 6]
Pump blocked
PumpAlarms/Warnings4.13
51
CUE, pump No [1; 6]
Power sensor signal fault
PumpAlarms/Warnings4.14
186
AI, pump No [1; 6]