English (GB)
74
An example is shown below
Event log
Hour log
• The "Hour log" button opens the display for showing the hour
log. The table below illustrates the structure of the data in the
Modbus registers and a way of visualising them.
ID
Code Description
Source
Type
Time
341
192
Overflow
System
Alarm appearing
05-08-2008 09:25
342
192
Overflow
System
Alarm disappearing
05-08-2008 11:09
343
222
Time for service, mixer
Mixer
Warning appearing
07-08-2008 02:38
344
6
Motor insulation resistance low
Pump 2
Warning appearing
11-08-2008 08:24
Note
The time stamp is in Unix time format. In the display
example, it has been converted to a human-readable
format.
Data
Hour
Registers
1
2
3
…
71
72
Pit overflow time [min.]
0
4
6
0
0
02001-02072
Number of pit overflows
0
1
3
0
0
02073-02144
Overflow volume [0.1 m
3
]
0
12
34
0
0
02145-02216
Specific energy [Wh/m
3
]
240
262
198
308
287
02217-02288
Pumped volume [m
3
]
67
69
72
45
23
02289-02360
Energy consumption [0.1 kWh]
342
456
514
178
123
02361-02432
Operating time (two pumps
operating simultaneously) [min.]
8
20
48
0
4
02433-02504
Pump 1, operating time [min.]
23
56
60
14
12
02793-02864
Pump 1, number of starts
4
1
1
4
3
02865-02936
Pump 1, average flow [0.1 l/s]
452
468
458
433
446
02937-03008
Pump 1, average current [0.1 A]
252
248
241
240
242
03009-03080
Pump 2, operating time [min.]
21
52
63
15
11
03081-03152
Pump 2, number of starts
7
2
1
2
3
03153-03224
Pump 2, average flow [0.1 l/s]
458
451
471
438
444
03225-03296
Pump 2, average current [0.1 A]
250
239
240
229
240
03297-03368
Pumpland.ru
Summary of Contents for CIM 200
Page 92: ...92 Pumpland ru...