English (GB)
20
00102
RelayControl
Bit 0: SetCustomRelay
Bool
Control bit that sets the value of the custom relay.
0 = Relay state logical 0
1 = Relay state logical 1.
CustomRelayPulse
Bit 1: PulseRelay
Bool
Control bit that pulses the custom relay. 0 (no pulse) will be the resulting
state.
0 = No pulse
1 = Pulse.
00103
PitPump1Control
Enum
Remote manual control of pump 1.
0 = "Auto" mode (the pump is controlled by the CU 36X)
1 = Forced start
2 = Forced stop.
00104
PitPump2Control
Enum
Remote manual control of pump 2.
0 = "Auto" mode (the pump is controlled by the CU 36X)
1 = Forced start
2 = Forced stop.
00105
PitPump3Control
Enum
Remote manual control of pump 3.
0 = "Auto" mode (the pump is controlled by the CU 36X)
1 = Forced start
2 = Forced stop.
00106
PitPump4Control
Enum
Remote manual control of pump 4.
0 = "Auto" mode (the pump is controlled by the CU 36X)
1 = Forced start
2 = Forced stop.
00107
PitPump5Control
Enum
Remote manual control of pump 5.
0 = "Auto" mode (the pump is controlled by the CU 36X)
1 = Forced start
2 = Forced stop.
00108
PitPump6Control
Enum
Remote manual control of pump 6.
0 = "Auto" mode (the pump is controlled by the CU 36X)
1 = Forced start
2 = Forced stop.
00109
ScadaPinCode
Unscaled
PIN code for SCADA systems, etc.
If PitStatus.ScadaPinCodeEnabled (register 00202, bit 4) is enabled, the
correct PIN code must be set in this register in order to gain access to
remote control and configuration.
Verify acceptance in PitStatus.WriteAccess (register 00202, bit 5).
00110
SetEventLogClearID
Unscaled
Selects which records to clear in the event log.
00111
SetInterlockTimeout
1 minute
Interlock timeout value measured in minutes.
Status of this register is read in InterlockTimeout (register 00226).
00112
SetRealTimeClockHI
1 second
Setting the real-time clock in the CU 36X in seconds since midnight January
1st 1970 (UNIX time).
First set SetRealTimeClockHI, then SetRealTimeClockLO in order to set a
new time in UNIX format.
00113
SetRealTimeClockLO
00114
SetRtcSecond
1 second
Real-time clock: Second of the minute [0; 59].
00115
SetRtcMinute
1 minute
Real-time clock: Minute of the hour [0; 59].
00116
SetRtcHour
1 hour
Real-time clock: Hour of the day [0; 23].
00117
SetRtcDay
1 day
Real-time clock: Day of the month [1; 31].
00118
SetRtcMonth
1 month
Real-time clock: Month of the year [1; 12].
00119
SetRtcYear
1 year
Real-time clock: Year [0; 254] = [year 2000; year 2254].
00120
SetRtc
Bit0: SetRtc
Bool
Control bit that sets the new real-time clock in the CU 36X.
1 = Set new real-time clock from the registers 00114 to 00119.
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
9.2 CIM configuration register block
, address 00005, for
acknowledgement behaviour.
00121
SetOverflowLevel
0.01 m
Setting a new level for activation of overflow level alarm.*
00122
SetHighLevel
0.01 m
Setting a new level for activation of high-level alarm.*
00123
SetAlarmLevel
0.01 m
Setting a new level for activation of alarm level alarm.*
00124
SetDryRunningLevel
0.01 m
Setting a new level for activation of dry-running alarm.*
00125
SetFoamDrainingLevel
0.01 m
Setting a new level for foam-draining stop.*
00126
SetStartLevelPump1
0.01 m
Setting a new start level, pump 1.*
00127
SetStopLevelPump1
0.01 m
Setting a new stop level, pump 1.*
00128
SetStartLevelPump2
0.01 m
Setting a new start level, pump 2.*
00129
SetStopLevelPump2
0.01 m
Setting a new stop level, pump 2.*
00130
SetStartLevelPump3
0.01 m
Setting a new start level, pump 3.*
00131
SetStopLevelPump3
0.01 m
Setting a new stop level, pump 3.*